PRE COMMISSIONING TEST PROCEDURE F0R LT PANEL
This procedure is prepared to carry out various pre- commissioning tests to be conducted in systematic manner for LT Panel to ensure the healthiness and performance of the LT Panel
Scope
This procedure covers the Pre commissioning test for LT Panel as for the following
- CRM Test for Circuit Breaker
- IR Test for Circuit Breaker
- Timer Test for Circuit Breaker
- CRM Test for Bus Bar
- IR Test for Bus Bar
- CT Test
- PT Test
Resources – Tools and Equipment Required
- For CRM Test:
- CRM kit
- Connecting cables
- Insulated Hand tools
- For Insulation Resistance measurement Test (IR Test):
- Test Leads
- 500 V, 5000 V Insulation Tester
- Insulated Hand Tools
- For Timing Measurement Test
- Timer Kit
- Testing leads
- Insulated Hand Tools
- Winding resistance test
- Multimeter with leads
- Coil Resistance measurement
Operational Sequence of work(Test Procedure)
Contact Resistance Measurement Test (Pole to Pole):
- Take the work permit from the client
- Ensure zero energy in the Bus Bar
- Keep the Breaker in closed condition
- Connect the earth from CRM kit to earth plate or earth pit
- Connect the CRM kit Current and Voltage leads across the Breaker contact R & R’
- Connect the CRM kit in A.C supply extension board with ELCB rated with 30 mA
- Inject the rated current to the Circuit Breaker
- Note down the contact resistance value from the CRM kit
- Repeat the above test for another phases (Y & Y’) & (B & B’)
- Switch off the power supply to the CRM Kit and disconnect them
DO’s | DON’TS |
|
|
IR TEST (BREAKER OPEN CONDITION)
- Keep the Circuit Breaker in open position
- Connect the IR kit across the RØ Breaker contact (R & R’)
- Select the required voltage range in IR kit
- Switch ON the IR kit and press the test button take down the reading
- Repeat the above steps for the other phases (YØ & BØ)
- Discharge the voltage from the Circuit Breaker with respect to
IR TEST BETWEEN PHASE TO EARTH (BREAKER CLOSED CONDITION)
- Keep the Circuit Breaker in closed position
- Connect the IR kit Positive lead with RØ Breaker contact
- Connect the IR kit Negative lead with earth
- Select the required voltage range in IR kit
- Switch ON the IR kit and press the test button take down the reading
- Repeat the above steps for the other phases (YØ & BØ)
- Discharge the voltage from the Circuit Breaker with respect to
DO’S | DON’TS |
|
|
Timing Test for circuit Breaker:
- Keep the Breaker in closed condition
- Connect the earth from Timer kit to earth plate or earth pit
- Connect the Timer kit feedback cables R and R’ leads across the RØ Breaker contact
- Connect the Timer kit feedback cables Y and Y’ leads across the YØ Breaker contact
- Connect the Timer kit feedback cables B and B’ leads across the BØ Breaker contact
- Connect the Timer kit in A.C supply extension board with ELCB rated with 30 mA
- Give The open command and note down the value from the timer kit
- Give the close command and note the value from the timer Kit
- Give the close/open command and note the value from the timer kit
- Switch off the power supply to the Timer Kit and disconnect them
DO’s | DON’TS |
|
|
Contact Resistance Measurement (CRM) Test – Bus Bar
- Take the work permit from the client
- Ensure zero energy in the Bus Bar
- Disconnect Bus bar from the transformer
- Connect the earth from CRM kit to earth plate or earth pit
- Connect the CRM kit voltage leads to across the(R-Phase) Bus Bar joint
- Connect the CRM kit current leads to across the(R-Phase) Bus Bar Joint, at the same time Voltage leads should be connected inside the current leads
- Ensure that all the connections are connected properly
- Connect the CRM kit in A.C supply extension board with ELCB rated with 30 mA
- Apply the rated current to the Bus bar
- Note down the resistance value from the CRM kit
- Repeat the above procedures for remaining (YØ & BØ)Phases for CRM Test
- Switch off the supply to the CRM Kit and disconnect the connections
DO’s | DON’TS |
|
|
IR TEST BETWEEN PHASE TO EARTH (BUS BAR):
- Check the Bus Bar tightness and panel earthing
- Connect the IR kit Positive lead with RØ Bus Bar
- Then connect the IR kit Negative lead with earth
- Select the required voltage range in IR kit
- Switch “ON” the IR kit and press the test button take down the reading
- Switch “OFF” the IR kit
- Discharge the potential from the bus bar with respect to earth
- Repeat the above steps for the other Bus bar phases (YØ & BØ)
IR TEST BETWEEN PHASE TO PHASE (BUS BAR):
- Connect the IR Kit across the RØ-YØ Bus Bar
- Select the required voltage range in IR kit
- Switch “ON” the IR kit and press the test button take down the reading
- Switch “OFF” the IR kit
- Discharge the potential from the Bus bar with respect to earth
- Repeat the above steps for the other Bus bar phases (YØ-BØ) &( BØ-RØ)
Do’s | Don’ts |
|
|
Insulation Resistance (IR) Test for CT Primary to Earth:
- Connect the Earth lead of the IR kit to the earth Terminal
- Connect HV lead of the IR kit to either P1 or P2 of the current Transformer
- Switch “ON” the IR kit and Select the required voltage range in IR kit
- press the Test button take down the readings
- Switch “OFF” the IR kit
Primary to Secondary:
- Connect HV lead of the IR kit to either P1 or P2 of the current Transformer
- Connect Earth lead of the IR kit to either S1 or S2 of the current Transformer
- Switch “ON” the IR kit and Select the required voltage range in IR kit
- press the Test button take down the readings
- Switch “OFF” the IR kit
Secondary to Earth:
- Connect Earth lead of the IR kit to the earth terminal
- Connect HV lead of the IR kit to either S1 or S2 of the current Transformer
- Switch “ON” the IR kit and Select the required voltage range in IR kit
- press the Test button take down the readings
- Switch “OFF” the IR kit
Between Secondary Cores:
- Connect HV lead of the IR kit to either S1 or S2 of the current Transformer
- Connect Earth lead of the IR kit to either S1 or S2 of the other core of the current Transformer
- Switch “ON” the IR kit and Select the required voltage range in IR kit
- press the Test button take down the readings
- Switch “OFF” the IR kit
- Discharge the voltage from the CT with respect to earth.
DO’S | DON’TS |
|
|
Polarity test for CT:
- Connect the secondary S1 terminal to galvanometer positive terminal and S2 to the negative terminal
- Touch the battery positive terminal to P1 in and negative terminal to the P2 terminal at the CT primary winding Terminals
- Check the deflection in the galvanometer
- It must be in clock-wise direction
DO’S | DONT’S |
|
|
Ratio test for CT
- Connect the variac and loading transformer
- Connect the loading transformer across the primary terminals(P1,P2)
- connect the variac in A.C supply extension board With ELCB rated with 30mA
- Inject the current across the primary terminals.
- Short Secondary
- Note down the corresponding secondary current at various cores.
- Switch off the supply to the primary injection kit
DO’S | DONT’S |
|
|